FC-PSU-UNI2450U V2.0 | HONEYWELL | Power Supply Unit
Specifications
Manufacturer: Honeywell
Product No.: FC-PSU-UNI2450U V2.0
Condition: 10 Items in Stock
Product Type: Power Supply Units
Product Origin: USA
Payment:T/T, Western Union
Weight: 7000g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The HONEYWELL FC-PSU-UNI2450U V2.0, also cataloged as the FC-PSU-UNI2450U V2.0 Power Supply Unit, operates as a dedicated hardware component for AC-to-DC power conversion and regulated backplane bus energization within Honeywell Safety Manager and Fail-Safe Controller (FSC) systems. Operating on a wide-range input of 110-240 VAC at 47-63 Hz, the module provides a factory-set output of 25 VDC (configurable up to 28 VDC) with dual overvoltage protection circuits and an integrated hold-up time of 100 ms at full load. The unit weighs 5.7 kg and operates reliably across an ambient temperature range of -5 to +70 deg C.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FC-PSU-UNI2450U V2.0 |
| Brand | Honeywell |
| Origin | Netherlands |
| Weight | 5.7 kg (Shipping weight: 7.0 kg) |
| Dimensions | Standard Safety Manager chassis power slot |
| Operating Temp | -5 to +70 deg C (23 to +158 deg F) |
| Power Consumption | 13 W at no load |
| Input Voltage Range | 110-240 VAC (47-63 Hz) |
| Inrush Current | Less than 15 A |
| Output Voltage | 25 VDC (default setting) or 28 VDC; dual overvoltage protection |
| Ripple and Noise | Less than 40 mVpp |
| Hold-up Time | 100 ms at full load |
| Efficiency | Greater than 87% at 230 VAC |
| Approvals | CE, TUV, UL, CSA, CID2 |
Channel-to-Channel Isolation & Power Conditioning
The FC-PSU-UNI2450U V2.0 integrates channel-to-channel isolation and low-noise power filtering to supply stable 25 VDC bus power to downstream analog and digital I/O modules. With output ripple and noise suppressed to less than 40 mVpp, the power supply prevents switching noise from coupling into high-accuracy 4-20 mA HART loop protocol circuits and sensitive field instrumentation. High-frequency galvanic isolation between the primary AC input stage and DC output rails protects sensitive system microprocessors from external power grid line surges and ground loop imbalances.
Frequently Asked Questions
Q: What happens to the system supply if the AC line voltage suffers a momentary interruption?
A: The internal capacitor bank provides a hold-up time of 100 ms at full load, maintaining stable 25 VDC output voltage through brief utility sags without triggering system reset or field loop fault alarms.
Q: How does the unit limit current draw during cold startup on AC mains?
A: An internal inrush current limiting circuit constrains the initial AC switch-on surge to under 15 A, preventing unwanted tripping of upstream branch circuit breakers.
Field Installation Guidelines
- Mount the FC-PSU-UNI2450U V2.0 module vertically into the designated Safety Manager power supply slot, locking all mechanical chassis latching mechanisms firmly.
- Terminate the primary 110-240 VAC input wiring into the screw terminal block, observing strict Phase, Neutral, and Protective Earth (PE) terminal assignments.
- Bond the module frame ground directly to the main cabinet earth bus using a short, low-impedance conductor to ensure full efficacy of the internal EMI filter and overvoltage protection networks.
- Maintain a minimum of 50 mm clearance above and below the module ventilation openings to allow uninhibited natural convection cooling across the internal heat sinks.