Description
Configured for safe discrete output control in Honeywell safety system architectures, the Honeywell FC-TSDO-0824C (FC-TSDO-0824C Safe Digital Output Module) provides direct physical/electrical execution. The module drives 8 discrete output channels, transferring safety-related switching commands from the logic solver backplane directly to field actuators and solenoids.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FC-TDSO-0824C |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.08 kg |
| Dimensions | 7 x 6 x 5.8 cm |
| Operating Temp | -20 to +60 deg C |
| Power Consumption | 24 VDC nominal (Load dependent; 1.5 A per channel max) |
| Module Function | Safe digital output signal control |
| Signal Type | Discrete DC output |
| Number of Channels | 8 channels |
| Maximum Voltage | 36 VDC (IEC 1010) |
| Max Continuous Current | 1.5 A per channel |
| Max Wire Diameter | 2.5 mm2 (AWG 14) |
| Approvals | CE, TUV, UL, CSA, FM |
Channel Isolation & Field Loop Characteristics
The FC-TSDO-0824C module incorporates channel-to-channel isolation and galvanic isolation barriers between the field wiring and internal backplane logic. The output switching hardware manages DC loads up to 36 VDC while sustaining up to 1.5 A continuous current per channel. Integrated protective filtering suppresses transient inductive spikes caused by de-energizing solenoid coils or field relays, preventing noise reflection back into the central safety logic solver.
Frequently Asked Questions
Q: What is the maximum continuous current capacity per output channel on the FC-TSDO-0824C module?
A: Each individual output channel supports a maximum continuous load current of 1.5 A at operating voltages up to 36 VDC, evaluated under IEC 1010 standards.
Q: What maximum conductor size is supported by the module termination connectors?
A: Terminal blocks on the module accommodate discrete field wiring up to a maximum cross-sectional area of 2.5 mm2 (AWG 14).
Field Installation Guidelines
- Mechanical Mounting: Seat the module firmly onto the dedicated safety rack baseplate guides inside the control cabinet until the retention latches fully engage.
- Wiring & Polarity: Terminate discrete load cables at the assigned terminal block. Verify matching DC voltage polarity and ensure conductor sizes do not exceed 2.5 mm2 (AWG 14).
- Shielding & Grounding: Connect field cable drain wires to the main enclosure earth grounding bar using low-impedance clamps to maintain common-mode noise suppression.
- Cable Routing: Maintain a minimum separation distance of 30 cm between 24 VDC digital output wiring and high-voltage AC power lines inside panel trunking.
How to Get a Quote