Description
The Honeywell FC-TSRO-08UNI is an 8-channel relay output field termination assembly designed for digital output signal processing in industrial automation systems. It interfaces controller output signals with higher-voltage or higher-current field devices while providing electrical isolation and output circuit protection.
Input Control and Switching Thresholds
The module operates at a nominal input control voltage of 24 Vdc, supporting a maximum input rating of 36 Vdc. The internal relays activate at a pick-up voltage threshold of 19.2 Vdc, ensuring positive contact switching and preventing unwanted actuation caused by control signal volt drops or floating inputs.
Output Contact Ratings and Protection
Equipped with 8 output channels, each output contact can switch loads up to 250 Vac or 250 Vdc. Each channel is individually fused to handle a maximum output current of 2 A, while supporting a minimum output switching threshold of 1 mA at 5 V for reliable low-power signaling.
| Parameter | Specification |
|---|---|
| Model | FC-TSRO-08UNI |
| Brand | Honeywell |
| Product Type | Digital Output Field Termination Assembly |
| Number of Channels | 8 (relay outputs) |
| Nominal Input Voltage | 24 Vdc |
| Max. Input Voltage | 36 Vdc |
| Relay Pick-Up Voltage | 19.2 Vdc |
| Max. Output Voltage | 250 Vac / 250 Vdc |
| Max. Output Current | 2 A (fused) |
| Min. Output Current | 1 mA at 5 V |
| Shipping Weight | 2 kg |
Frequently Asked Questions
Q: What are the primary input activation limits for the FC-TSRO-08UNI?
A: The assembly operates at a nominal input voltage of 24 Vdc with a maximum voltage limit of 36 Vdc, and the relay pick-up voltage triggers reliably at 19.2 Vdc.
Q: What contact load capacity does each output channel support?
A: Each output channel handles up to 250 Vac or 250 Vdc with a fused maximum current of 2 A, and can switch low-level signals down to 1 mA at 5 V.