{"product_id":"foxboro-fbm215-p0916db-hart-communication-output-module","title":"Foxboro FBM215 P0916DB HART Communication Output Module","description":"\u003cp\u003eThe \u003cstrong\u003eFBM215 P0916DB\u003c\/strong\u003e is a Foxboro HART communication output module with up to 8 isolated channels supporting HART Version 5, 6, and 7 field instruments. It communicates over a redundant 2 Mbps module fieldbus with FCM or FCP modules, runs on 24 VDC (+-5%) power at up to 7 W consumption, and operates from -20 deg C to +70 deg C.\u003c\/p\u003e\n\u003ch3\u003eHART Field Communication and Fieldbus Link\u003c\/h3\u003e\n\u003cp\u003eOn the field side, the \u003cstrong\u003eFBM215 P0916DB\u003c\/strong\u003e provides up to 8 isolated output channels using point-to-point, master\/slave, asynchronous, half-duplex communication at 1200 baud. Each message transfers at up to 2 messages per second with per-byte parity plus a CRC check byte per message, making cycle timing and HART device polling rates relevant factors when configuring multi-loop instrumentation.\u003c\/p\u003e\n\u003cp\u003eOn the system side, the module connects via a redundant 2 Mbps module fieldbus with FCM or FCP modules. Confirm supported HART device versions, loop timing, and fieldbus topology rules in your control system engineering documentation before deployment.\u003c\/p\u003e\n\u003ch3\u003ePower and Operating Limits\u003c\/h3\u003e\n\u003cp\u003eInput power is rated at 24 VDC (+-5%) with a maximum power consumption of 7 W and maximum heat dissipation of 5 W. Include both the 7 W power draw and 5 W thermal output in cabinet power supply and cooling calculations.\u003c\/p\u003e\n\u003cp\u003eModule operating temperature spans -20 deg C to +70 deg C (-4 deg F to +158 deg F), while PVC termination assembly temperature is rated from -20 deg C to +50 deg C (-4 deg F to +122 deg F). Relative humidity is 5% to 95% non-condensing, and altitude is rated from -300 to +3000 m (-1000 to +10,000 ft).\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFBM215 P0916DB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eFoxboro\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eHART Communication Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Channels\u003c\/td\u003e\n\u003ctd\u003eUp to 8 isolated output channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported HART Versions\u003c\/td\u003e\n\u003ctd\u003eVersion 5, 6, 7 instruments\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHART Communication Mode\u003c\/td\u003e\n\u003ctd\u003ePoint-to-point, master\/slave, asynchronous, half-duplex, 1200 baud\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHART Error Checking\u003c\/td\u003e\n\u003ctd\u003eParity per byte + CRC check byte per message\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHART Speed\u003c\/td\u003e\n\u003ctd\u003e2 messages per second\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFieldbus Protocol\u003c\/td\u003e\n\u003ctd\u003eRedundant 2 Mbps module fieldbus with FCM or FCP\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC (+-5%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e7 W max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHeat Dissipation\u003c\/td\u003e\n\u003ctd\u003e5 W max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Operating Temperature\u003c\/td\u003e\n\u003ctd\u003e-20 deg C to +70 deg C (-4 deg F to +158 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination Assembly Temperature (PVC)\u003c\/td\u003e\n\u003ctd\u003e-20 deg C to +50 deg C (-4 deg F to +122 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAltitude\u003c\/td\u003e\n\u003ctd\u003e-300 to +3000 m (-1000 to +10,000 ft)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: Which HART instrument versions and communication rates does the Foxboro FBM215 P0916DB support?\u003c\/p\u003e\n\u003cp\u003eA: It supports HART Version 5, 6, and 7 instruments over up to 8 isolated output channels at 1200 baud (point-to-point, master\/slave, asynchronous, half-duplex) and up to 2 messages per second. Verify device compatibility and message scan timing against your control loop requirements during engineering design.\u003c\/p\u003e\n\u003cp\u003eQ: Why does the source list different temperature limits for the module and the termination assembly?\u003c\/p\u003e\n\u003cp\u003eA: The module itself is rated from -20 deg C to +70 deg C (-4 deg F to +158 deg F), whereas the PVC termination assembly is rated from -20 deg C to +50 deg C (-4 deg F to +122 deg F). Keep both the module and its termination assembly within their respective temperature limits in the cabinet.\u003c\/p\u003e\n\u003cp\u003eQ: What input power and fieldbus interface are specified for the FBM215 P0916DB?\u003c\/p\u003e\n\u003cp\u003eA: It requires 24 VDC (+-5%) input power with up to 7 W consumption and 5 W heat dissipation, and uses a redundant 2 Mbps module fieldbus with FCM or FCP. Confirm power budget capacity and compatible FCM\/FCP hardware in your system configuration.\u003c\/p\u003e","brand":"Foxboro","offers":[{"title":"Default Title","offer_id":68237090193704,"sku":"FBM215 P0916DB","price":238.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/FBM215P0922VU_4ae9d307-9ef2-447b-bb3a-0aa98007cb6d.png?v=1795069833","url":"https:\/\/www.powerdcs.com\/products\/foxboro-fbm215-p0916db-hart-communication-output-module","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}