{"product_id":"foxboro-fbm230-p0926gu-field-device-system-integrator-module","title":"Foxboro FBM230 P0926GU Field Device System Integrator Module","description":"\u003cp\u003eThe \u003cstrong\u003eFBM230 P0926GU\u003c\/strong\u003e is a Foxboro I\/A Series field device system integrator module with four software-configurable serial ports for RS-232, RS-422, or RS-485 communications. Powered by redundant 24 VDC (+5%, -10%) with a 7 W maximum draw, it links external serial devices to Foxboro control databases over a redundant 2 Mbps module fieldbus.\u003c\/p\u003e\n\u003ch3\u003eSerial Ports, Capacity, and Protocol Drivers\u003c\/h3\u003e\n\u003cp\u003eEach of the four serial ports on the \u003cstrong\u003eFBM230 P0926GU\u003c\/strong\u003e can be configured independently in software for RS-232, RS-422, or RS-485 operation. I\/O software drivers can be downloaded from a library of supported protocols to integrate field device data into a Foxboro control database.\u003c\/p\u003e\n\u003cp\u003eThe module supports up to 200 DCI block connections and handles up to 64 RS-485 devices or up to 4 direct-connect RS-232 or RS-422 devices. Plan port assignments and device counts around protocol overhead and serial bus topology limits during system engineering.\u003c\/p\u003e\n\u003ch3\u003eSystem Bus, Power, and Cabling Limits\u003c\/h3\u003e\n\u003cp\u003eOn the system side, the \u003cstrong\u003eFBM230 P0926GU\u003c\/strong\u003e communicates over a redundant 2 Mbps module fieldbus with associated FCM100ET, FCM100E, FCP270, or FCP280 modules. Redundant 24 VDC input power is rated for +5%, -10% tolerance with up to 7 W power consumption and 7 W heat dissipation.\u003c\/p\u003e\n\u003cp\u003eTermination assemblies connect to the module via Type 5 termination cables in lengths from 1 m (3.2 ft) to 5 m (16.4 ft). Field cable runs reach up to 15 m (50 ft) for custom EIA RS-232 DB-25 connections to modems, converters, or devices, and up to 1200 m (3937 ft) for RS-422 and RS-485 links.\u003c\/p\u003e\n\u003ch3\u003eEnvironmental and Mechanical Considerations\u003c\/h3\u003e\n\u003cp\u003eThe module is designed for field mounting and rated for Class G3 harsh environments, operating from -20 deg C to +70 deg C (-4 deg F to +158 deg F) with 5% to 95% non-condensing relative humidity. Storage temperature spans -40 deg C to +70 deg C (-40 deg F to +158 deg F) under 5% to 95% non-condensing humidity.\u003c\/p\u003e\n\u003cp\u003eModule dimensions are 102 mm (4 in) high—114 mm (4.5 in) with mounting lugs—by 45 mm (1.75 in) wide by 104 mm (4.11 in) deep, with an approximate mass of 284 g (10 oz). Listed termination assemblies include ring lug P0926PA (approximately 363 g \/ 0.8 lb) and compression screw RH926GH (approximately 272 g \/ 0.6 lb).\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFBM230 P0926GU\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eFoxboro\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eField Device System Integrator Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eI\/A Series\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSerial Ports\u003c\/td\u003e\n\u003ctd\u003e4 ports, individually configurable in software for RS-232, RS-422, or RS-485\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice Capacity\u003c\/td\u003e\n\u003ctd\u003eUp to 64 RS-485 devices or up to 4 direct-connect RS-232 or RS-422 devices\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDCI Block Capacity\u003c\/td\u003e\n\u003ctd\u003eUp to 200 DCI block connections\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Fieldbus\u003c\/td\u003e\n\u003ctd\u003eRedundant 2 Mbps module fieldbus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAssociated Modules\u003c\/td\u003e\n\u003ctd\u003eFCM100ET, FCM100E, FCP270, or FCP280\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Range (Redundant)\u003c\/td\u003e\n\u003ctd\u003e24 VDC (+5%, -10%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e7 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHeat Dissipation\u003c\/td\u003e\n\u003ctd\u003e7 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination Cable\u003c\/td\u003e\n\u003ctd\u003eType 5, 1 m (3.2 ft) to 5 m (16.4 ft) between FBM230 and TA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Cable Distance\u003c\/td\u003e\n\u003ctd\u003eUp to 15 m (50 ft) custom RS-232 (DB-25); up to 1200 m (3937 ft) RS-422 and RS-485\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination Assemblies\u003c\/td\u003e\n\u003ctd\u003eRing Lug P0926PA (approx. 363 g \/ 0.8 lb); Compression Screw RH926GH (approx. 272 g \/ 0.6 lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Dimensions\u003c\/td\u003e\n\u003ctd\u003e102 mm (4 in) H (114 mm \/ 4.5 in with mounting lugs) x 45 mm (1.75 in) W x 104 mm (4.11 in) D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Mass\u003c\/td\u003e\n\u003ctd\u003eApprox. 284 g (10 oz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-20 deg C to +70 deg C (-4 deg F to +158 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +70 deg C (-40 deg F to +158 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnvironmental Rating\u003c\/td\u003e\n\u003ctd\u003eClass G3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: How many serial devices can the Foxboro FBM230 P0926GU connect to?\u003c\/p\u003e\n\u003cp\u003eA: It supports up to 64 RS-485 devices or up to 4 direct-connect RS-232 or RS-422 devices across its four software-configurable ports, within a limit of up to 200 DCI block connections. Actual device counts also depend on the selected protocol driver and serial network layout.\u003c\/p\u003e\n\u003cp\u003eQ: Which termination assemblies and cable lengths apply to the FBM230 P0926GU?\u003c\/p\u003e\n\u003cp\u003eA: The source lists ring lug termination assembly P0926PA and compression screw termination assembly RH926GH, connected via Type 5 cables from 1 m (3.2 ft) to 5 m (16.4 ft). Field runs can extend up to 15 m (50 ft) for custom RS-232 DB-25 links and up to 1200 m (3937 ft) for RS-422 and RS-485.\u003c\/p\u003e\n\u003cp\u003eQ: What power supply and fieldbus connections does the FBM230 P0926GU use?\u003c\/p\u003e\n\u003cp\u003eA: It uses redundant 24 VDC (+5%, -10%) power at up to 7 W maximum and communicates over a redundant 2 Mbps module fieldbus with FCM100ET, FCM100E, FCP270, or FCP280 modules. Verify power redundancy and fieldbus compatibility within your Foxboro I\/A Series configuration.\u003c\/p\u003e","brand":"Foxboro","offers":[{"title":"Default Title","offer_id":68233677177128,"sku":"FBM230 P0926GU","price":238.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/FBM230.jpg?v=1795054521","url":"https:\/\/www.powerdcs.com\/products\/foxboro-fbm230-p0926gu-field-device-system-integrator-module","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}