FS-TSGAS-1624 Fail-Safe Gas-Flame Detector Input Field Termination Assembly | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: FS-TSGAS-1624
Condition: 10 Items in Stock
Product Type: Gas-Flame Detector Input FTA
Product Origin: USA
Payment:T/T, Western Union
Weight: 3000g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell FS-TSGAS-1624 is a 16-channel fail-safe gas-flame detector input field termination assembly (FTA). It functions as a dedicated signal conditioning interface, receiving analog transmitter signals from field-mounted gas and flame detectors and converting them for safety system processing modules.
Analog Signal Processing and Output Conditioning
The assembly supports 16 analog input channels rated for 0-20 mA current loops with a common 0 V reference. Featuring an internal input resistance of 500 Ω ±5%, the assembly conditions incoming field currents into a proportional 0-4 VDC voltage output signal directed to the connected SAI-1620m safety analog input module, maintaining high signal precision with 0.1% accuracy.
Power Requirements
The module operates from an external 24 VDC power supply. Without accounting for field load currents, the internal circuitry of the assembly draws a baseline current of 3 mA during standard operation.
| Parameter | Specification |
|---|---|
| Model | FS-TSGAS-1624 |
| Brand | Honeywell |
| Product Type | Fail-Safe Gas-Flame Detector Input Field Termination Assembly |
| Input Channels | 16 analog inputs (0-20 mA) with common 0 V reference |
| Input Resistance | 500 Ω ±5% |
| Signal Conversion Output | 0-4 VDC to SAI-1620m module |
| Signal Accuracy | 0.1% |
| Power Supply | 24 VDC external |
| Base Power Consumption | 3 mA (without field loads) |
| Shipping Weight | 3 kg |
Frequently Asked Questions
Q: Which input module does the FS-TSGAS-1624 interface with?
A: The assembly conditions 0-20 mA field signals into a 0-4 VDC output specifically designed for connection to the Honeywell SAI-1620m module.
Q: What power source is required to operate the FS-TSGAS-1624?
A: It requires an external 24 VDC power supply, drawing a base current of 3 mA excluding connected field device loads.