FS-TSRO-0824 Honeywell Digital Output Field Termination Assembly
Specifications
Manufacturer: Honeywell
Product No.: FS-TSRO-0824
Condition: 10 Items in Stock
Product Type: Digital Output Modules
Payment:T/T, Western Union
Weight: 2000g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
Configured for discrete relay output switching and high-current load execution in Honeywell Safety Manager systems, the Honeywell FS-TSRO-0824 (FS-TSRO-0824 Digital Output Field Termination Assembly) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FS-TSRO-0824 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 2.00 kg (Shipping weight) |
| Dimensions | 300 mm x 70 mm x 60 mm (L x W x H) |
| Operating Temp | -20 deg C to +60 deg C |
| Power Consumption | Typically 40 mA at 24 VDC per energized relay coil |
| Channels | 8 relay output channels |
| Nominal Input Voltage | 24 VDC (36 VDC max. input voltage) |
| Relay Pick-Up Voltage | 19.2 VDC |
| Max Switched Voltage | 250 VAC / 250 VDC |
| Max Switched Current | 5 A per channel (fused) |
| Min Switched Current | 1 mA at 5 VDC |
| Max Switched Power | 1250 VA / 150 W |
| Safety Classification | AK1-6 (TUV, CE, UL pending) |
4-20 mA HART Loop Protocol and Channel-to-Channel Isolation
The field termination module incorporates galvanic isolation barriers between the 24 VDC control side relay coils and output contacts, maintaining strict channel-to-channel isolation across all 8 switching channels. Physical isolation prevents high-voltage AC switching transients and inductive kickback on field output lines from coupling into sensitive 4-20 mA HART loop protocol analog input signals or backplane logic buses operating within adjacent chassis racks.
Frequently Asked Questions
Q: What protection is provided for individual output switching channels on the FS-TSRO-0824?
A: Each of the 8 output channels features an integrated 5 A fuse to protect relay contacts and field wiring from overcurrent conditions.
Q: What is the minimum activation threshold required for reliable relay coil energization?
A: The relay pick-up voltage is specified at 19.2 VDC, below which the relay contacts will remain in their de-energized shelf state.
Q: Can the FS-TSRO-0824 switch both AC and DC field loads?
A: Yes, the dry relay contacts support switching up to 250 VAC (1250 VA max) or 250 VDC (150 W max) per channel.
Field Installation Guidelines
- Mount the assembly on standard DIN rails within the control cabinet, ensuring vertical orientation to facilitate free convection cooling.
- Verify that field output load currents do not exceed the 5 A continuous channel rating prior to connecting field field wiring terminals.
- Connect inductive AC or DC loads with parallel suppressor elements (RC networks or flyback diodes) across field field contacts to suppress arc discharge and extend contact lifecycle.
- Maintain separate wire channels for 24 VDC control cables and high-voltage 250 VAC output wiring to prevent cross-talk and electromagnetic induction.