GE IS220PAICH1BG (IS230SNAIH2A) Analog Input/Output Pack
Specifications
Manufacturer: GE
Product No.: IS220PAICH1BG
Condition: 10 Items in Stock
Product Type: Analog Input/Output Pack
Product Origin: USA
Payment:T/T, Western Union
Weight: 350g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
IS220PAICH1B | GE Analog I/O Module (Mark VI Series)
Manufacturer: General Electric
Product Type: Analog Input/Output Module
Series: Mark VI
Functional Acronym: PAIC
Model Revision: IS220PAICH1B (B-rated functional revision)
Certifications:
-
Non-Hazardous: UL E207685
-
Hazardous Locations (ATEX Zone 2, Group IIC):
-
EN 60079-0:2018
-
EN 60079-7:2015
-
EN 60079-11:2012
Overview
The IS220PAICH1B is a second-generation analog I/O pack from GE’s Mark VI turbine control series. It is engineered to deliver accurate and reliable analog signal acquisition and transmission. Designed for both hazardous and non-hazardous industrial environments, this module supports multiple terminal board options and provides diagnostic capabilities to ensure system integrity.
Key Technical Specifications
-
Ambient Operating Temperature: –40°F to 158°F (–40°C to 70°C)
-
Analog Transmitter Power: 22.8 VDC
-
Nominal Power Supply: 24V or 28V DC
-
Minimum Voltage Requirement: 22.5 VDC
-
Delta Method: Percentage of Configured Span
-
Wire Requirements: Minimum 22 AWG (when connected via IS200TBAIH1C terminal board)
Compatible Terminal Boards
The IS220PAICH1B pack is compatible with the following GE IS200 terminal boards:
-
IS200TBAIH1C (Barrier-type terminal board)
-
IS200TAIH1A
-
IS200TAIH2A
Pack Diagnostics & Alarms
Alarm 66–67:
-
Description: Individual output current is too high relative to the total current.
-
Indicates: Potential signal imbalance or malfunction.
Alarm 82–83:
-
Description: Suicide relay is non-functional.
-
Possible Causes:
-
Mismatch between relay command and feedback
-
Hardware failure
-
Acquisition board relay failure
-
Recommended Action: Replace the I/O pack
Product Notes
-
The IS220PAICH1B is a successor to the IS220PAICH1 and differs in minimum voltage requirement and revision.
-
While part of the Mark VI platform, its legacy also aligns with the Mark V turbine control system architecture.
-
This module is part of a broader GE control ecosystem and integrates easily with legacy and modern systems alike.