GE IS220PAICH1BG (IS230SNAIH2A) Analog Input/Output Pack

Specifications

  • Manufacturer: GE

  • Product No.: IS220PAICH1BG

  • Condition: 10 Items in Stock

  • Product Type: Analog Input/Output Pack

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 350g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

IS220PAICH1B | GE Analog I/O Module (Mark VI Series)

Manufacturer: General Electric
Product Type: Analog Input/Output Module
Series: Mark VI
Functional Acronym: PAIC
Model Revision: IS220PAICH1B (B-rated functional revision)
Certifications:

  • Non-Hazardous: UL E207685

  • Hazardous Locations (ATEX Zone 2, Group IIC):

    • EN 60079-0:2018

    • EN 60079-7:2015

    • EN 60079-11:2012


Overview

The IS220PAICH1B is a second-generation analog I/O pack from GE’s Mark VI turbine control series. It is engineered to deliver accurate and reliable analog signal acquisition and transmission. Designed for both hazardous and non-hazardous industrial environments, this module supports multiple terminal board options and provides diagnostic capabilities to ensure system integrity.


Key Technical Specifications

  • Ambient Operating Temperature: –40°F to 158°F (–40°C to 70°C)

  • Analog Transmitter Power: 22.8 VDC

  • Nominal Power Supply: 24V or 28V DC

  • Minimum Voltage Requirement: 22.5 VDC

  • Delta Method: Percentage of Configured Span

  • Wire Requirements: Minimum 22 AWG (when connected via IS200TBAIH1C terminal board)


Compatible Terminal Boards

The IS220PAICH1B pack is compatible with the following GE IS200 terminal boards:

  • IS200TBAIH1C (Barrier-type terminal board)

  • IS200TAIH1A

  • IS200TAIH2A


Pack Diagnostics & Alarms

Alarm 66–67:

  • Description: Individual output current is too high relative to the total current.

  • Indicates: Potential signal imbalance or malfunction.

Alarm 82–83:

  • Description: Suicide relay is non-functional.

  • Possible Causes:

    • Mismatch between relay command and feedback

    • Hardware failure

    • Acquisition board relay failure

  • Recommended Action: Replace the I/O pack


Product Notes

  • The IS220PAICH1B is a successor to the IS220PAICH1 and differs in minimum voltage requirement and revision.

  • While part of the Mark VI platform, its legacy also aligns with the Mark V turbine control system architecture.

  • This module is part of a broader GE control ecosystem and integrates easily with legacy and modern systems alike.

 