Honeywell 10206/2/1 Digital Output Module
Specifications
Manufacturer: Honeywell
Product No.: 10206/2/1
Condition: 10 Items in Stock
Product Type: Digital Output Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 230g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell 10206/2/1 is a 12-channel digital output module designed for industrial automation control architectures. It provides discrete switching signals to drive both resistive loads, such as indicator lamps, and inductive loads, such as solenoids, up to 13 W per channel.
Output Grouping and Power Configuration
The module features 12 output channels organized into two independent groups of six outputs, allowing separate external power supplies to energize each group. Operating from a 24V DC supply, each channel supports a maximum continuous current of 550 mA with an off-state leakage current below 0.1 mA.
Inductive Protection and System Safety
Each output incorporates built-in suppression diodes to safely handle inductive kickback currents generated by switching solenoids or relays. In the event of a system shutdown or controller failure, the integrated watchdog control mechanism automatically de-energizes the outputs. This specific model variant is not tested for certified fail-safe applications.
| Parameter | Specification |
|---|---|
| Model | 10206/2/1 |
| Brand | Honeywell |
| Product Type | Digital Output Module |
| Number of Output Channels | 12 |
| Output Groups | Two groups of six outputs (independently powered) |
| Supply Voltage | 24V DC (two independent external supplies) |
| Maximum Current per Channel | 550 mA |
| Load Capacity | Up to 13W per channel |
| Off-State Current | < 0.1 mA |
| Inductive Protection | Integrated suppression diodes |
| Watchdog Control | Outputs de-energize upon system shutdown |
| Fail-Safe Compliance | Not tested for fail-safe applications |
Frequently Asked Questions
Q: How are the output channels powered on the Honeywell 10206/2/1?
A: The 12 output channels are split into two groups of six, each powered independently by separate 24V DC external supplies.
Q: What happens to the outputs if the control system shuts down?
A: Integrated watchdog control ensures that all outputs automatically de-energize if a system shutdown occurs.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions