Honeywell 51191699-100 Switch / Proximity Detector Interface
Specifications
Manufacturer: Honeywell
Product No.: 51191699-100
Condition: 10 Items in Stock
Product Type: Proximity Detector Interfaces
Product Origin: USA
Payment:T/T, Western Union
Weight: 120g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell 51191699-100 (MTL4016) is a dedicated hardware component engineered for intrinsic safety signal conditioning and discrete status monitoring within Honeywell distributed control systems. It translates binary field states from hazardous areas into reliable control inputs for safe-area logic solvers.
Signal Processing and Isolation
The module processes discrete inputs from field-mounted NAMUR proximity detectors or dry contact switches, providing safe signal transmission to DCS digital input systems. Built-in galvanic isolation prevents ground current loops and suppresses differential voltage spikes across field terminal lines, protecting sensitive control hardware from hazardous area faults.
Electrical and Environmental Ratings
Operating on a power supply range of 20 to 35 VDC with a maximum current draw of 30 mA, the unit delivers open-collector transistor outputs. It is built to an IP20 enclosure rating and functions within an ambient temperature range of -20 deg C to +60 deg C.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 51191699-100 (MTL4016) |
| Brand | Honeywell / MTL |
| Power Consumption | 20 to 35 VDC (30 mA maximum) |
| Sensor Inputs | Switch contacts or NAMUR proximity detectors |
| Output Type | Open-collector transistor outputs |
| Isolation | 250 VAC input-to-output galvanic isolation |
| Enclosure Rating | IP20 |
| Operating Temp | -20 deg C to +60 deg C |
| Dimensions | 17.5 mm x 114.0 mm x 119.0 mm |
| Weight | 0.12 kg (0.26 lbs) |
| Origin | France |
Field Installation Guidelines
DIN-Rail Mounting: Snap the module housing onto standard EN 60715 DIN-rail carriers within a protective enclosure. Hazardous Wiring Separation: Maintain strict physical segregation between hazardous area field wiring and safe-area output cabling. Shield Grounding: Connect field cable shields to the main cabinet functional earth busbar at a single earthing point to prevent loop currents. Thermal Ventilation: Ensure at least 10 mm of clear airspace above and below the module housing to enable passive convection cooling within the cabinet.
Frequently Asked Questions
Q: Can the 51191699-100 module be installed or replaced on an energized backplane?
A: Yes. The unit features safe-area plug-in edge pin connectors designed for live-insertion and removal without disrupting neighboring signal conditioning channels.
Q: What type of field sensors are compatible with the input terminals of the 51191699-100?
A: The input channels support standard NAMUR proximity switches or volt-free dry contacts located in intrinsically safe zones.