Honeywell 8U-PAIH54 Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: 8U-PAIH54
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 400g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell 8U-PAIH54, also cataloged as the 8U-PAIH54 Analog Input Module, operates as a dedicated hardware component for high-precision 16-channel analog signal acquisition within Honeywell Experion PKS Series C platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 8U-PAIH54 |
| Brand | Honeywell |
| Origin | United States |
| Weight | 0.40 kg nominal |
| Dimensions | Standard Series C Module Footprint |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 7.5 W |
| Input Channels | 16 channels (Single-ended or differential) |
| Input Signal Range | 1-5 VDC, 4-20 mA (via external 250 Ohm resistor) |
| A/D Resolution | 16 bits |
| Scan Rate | 50 ms |
| Supply Voltage | 24 VDC |
| Current Consumption | 310 mA |
| Accuracy | +/-0.075% full scale (at 23.5 deg C), +/-0.15% full scale (0 to 60 deg C) |
| Channel Crosstalk | -60 dB (DC to 60 Hz) |
4-20 mA HART Loop Protocol Pass-Through and Channel Isolation
The Honeywell 8U-PAIH54 incorporates internal differential input architecture and an integrated single-pole RC filter (-3 dB at 6.5 Hz) to execute channel-to-channel isolation and eliminate common-mode noise propagation across process loops. The module hardware natively supports 4-20 mA HART loop protocol pass-through, extracting digital diagnostic data, secondary variables, and calibration metadata from smart field transmitters directly into the controller database without interfering with the primary 16-bit analog-to-digital scan cycle.
Frequently Asked Questions
Q: Does the 8U-PAIH54 module support online hot-swapping during system execution?
A: Yes, the module supports Removal and Insertion Under Power (RIUP) on active IOTA platforms, allowing field maintenance without interrupting control backplane operations.
Q: How is a 4-20 mA current signal converted into the module input range?
A: A 4-20 mA input loop requires a 250 Ohm precision resistor across the input terminals to convert the current loop into a corresponding 1-5 VDC voltage signal for the 16-bit A/D converter.
Q: What mechanism rejected electromagnetic interference on field wiring runs?
A: The board incorporates differential input signal routing combined with an onboard RC filter providing -60 dB crosstalk suppression from DC to 60 Hz.
Field Installation Guidelines
- Align and insert the module firmly onto the designated IOTA base, ensuring complete mechanical latching to establish proper backplane ground.
- Terminate all incoming 4-20 mA and 1-5 VDC field signal lines using twisted shielded pair cabling to minimize external RFI noise coupling.
- Connect signal cable shields at a single point on the cabinet instrument earth bus bar; do not ground shields at both ends to avoid ground loops.
- Maintain recommended spatial gaps between adjacent modules to facilitate vertical convection cooling within the Series C enclosure.
- Verify that all field conduit connections maintain a minimum of 5 full threads of NPT engagement to preserve mechanical junction seal integrity.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions
Related Products