Honeywell 8U-PWSP05 Series 8 Power Supply Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: 8U-PWSP05

  • Condition: 10 Items in Stock

  • Product Type: Power Supply Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 560g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

Configured for 24 VDC system power generation and distribution in Experion PKS Series 8 platforms, the Honeywell 8U-PWSP05 (8U-PWSP05 Power Supply Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model 8U-PWSP05
Brand Honeywell
Origin USA
Operating Temp 0 deg C to 70 deg C
Power Consumption Power supply output rated at 20 A at 24 VDC
Module Type Power Supply Module
Input Voltage Range 85-264 VAC
Output Voltage 22.5-29.5 VDC
Output Current 0-20 A
Efficiency @ 120V AC 91.0%
Efficiency @ 230V AC 91.0%
Power Factor 0.99 (@ 120 VAC / 230 VAC)
Holdup Time >13 ms (@ 120 VAC / 230 VAC)
Thermal Limits Maximum rate of change 1 deg C/min

Process Loop Power Management and Channel Isolation

The Honeywell 8U-PWSP05 converts incoming wide-range AC power into a regulated 22.5-29.5 VDC bus to power field instruments operating on 4-20 mA HART loop protocol configurations. Built-in primary-to-secondary galvanic isolation prevents high-voltage grid transients from entering the Series 8 control plane or field instrumentation loops. The internal architecture provides automatic channel-to-channel isolation and output protection features, including active overcurrent and overvoltage clamps. A holdup time greater than 13 ms maintains stable 24 VDC rails across power dip events without disrupting transmitter signal conditioning or output driver execution.

Frequently Asked Questions

Q: What input AC voltage range can the 8U-PWSP05 module accept?

A: The module operates across a universal input supply range from 85 to 264 VAC without manual tap or jumper changes.

Q: How does the 8U-PWSP05 handle transient utility power interruptions?

A: Internal storage capacitors provide a holdup time exceeding 13 ms at both 120 VAC and 230 VAC inputs to keep the 24 VDC output bus stabilized during brief mains drops.

Q: What environmental thermal change rate limit applies to the module enclosure?

A: The module specifies a maximum ambient temperature rate of change limit of 1 deg C/min within its 0 deg C to 70 deg C operating window.

Field Installation Guidelines

  1. Confirm that main AC power sources are isolated and locked out before wiring primary terminals.
  2. Align the module card edges with the card guide rails of the designated Series 8 power assembly slot.
  3. Push the module securely into position until the rear interface terminals fully seat into the backplane connectors.
  4. Fasten top and bottom module retaining screws to secure mechanical locking and chassis ground contact.
  5. Connect input wiring (85-264 VAC) adhering to line, neutral, and earth terminal assignments, ensuring the protective earth lead connects to the main ground bus using short, low-impedance grounding straps.
  6. Check output voltage adjustment settings (22.5-29.5 VDC) prior to energizing connected field loops and I/O channels