Honeywell 900A16-0103 ControlEdge 900 High Level Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: 900А16-0103
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Payment:T/T, Western Union
Weight: 450g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
Configured for high-density analog voltage signal acquisition in ControlEdge 900 platform architectures, the Honeywell 900A16-0103 (900A16 High Level Analog Input Module) provides direct physical/electrical execution of 16-channel high-level sensor inputs.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 900A16-0103 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.45 kg (1.00 lbs) |
| Dimensions | Standard ControlEdge 900 module form factor |
| Operating Temp | 0 to +60 deg C |
| Power Consumption | 75 mA max at 5 VDC and 50 mA max at 24 VDC |
| Product Type | Analog Input Modules |
| Secondary Part Number | 50008235-002 |
| Channel Density | 16 channels |
| Input Signal Range | +/- 10 VDC |
| Update Rate | 100 ms |
| Leakage Current | 2 uA max/channel |
| System Compatibility | Honeywell ControlEdge 900 |
4-20 mA HART Loop Protocol and Channel-to-Channel Isolation
The 900A16-0103 module acquires +/- 10 VDC high-level voltage inputs across 16 isolated channels with a 100 ms scan execution time. Built to integrate within process control racks processing 4-20 mA HART loop protocol instruments, the module input circuitry enforces strict channel-to-channel isolation. This limits current leakage to 2 uA max per channel, preventing signal attenuation and electrical ground loops across differential measurement points.
Frequently Asked Questions
Q: What are the backplane power supply current requirements for the 900A16-0103 module?
A: The module draws a maximum backplane load of 75 mA at 5 VDC and 50 mA at 24 VDC.
Q: What is the maximum channel scan rate for the 16 analog input signals?
A: All 16 channels are processed continuously with an update interval of 100 ms.
Field Installation Guidelines
- Power down the controller rack backplane before inserting or removing the module from its slot.
- Route high-level voltage signal wiring using twisted-pair shielded cable, grounding the cable shield at a single termination point on the rack chassis.
- Keep field input conductors separated from high-voltage AC cables in wire ducts to prevent capacitive crosstalk.
- Verify all field wiring terminals are fully seated and tightened to prevent loose high-resistance analog sensor connections.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions
Related Products