Honeywell CC-PAIH02 51405039-175 Experion PKS Analog Input Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: CC-PAIH02 51405039-175

  • Condition: 10 Items in Stock

  • Product Type: Analog Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 450g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

Configured for high-level signal acquisition in Experion PKS Series-C control systems, the Honeywell CC-PAIH02 51405039-175 (CC-PAIH02 Analog Input Module) provides direct physical/electrical execution. It handles 16 analog input channels across Input/Output Termination Assembly (IOTA) backplane networks.

Hardware Specifications

Parameter Specification
Model CC-PAIH02 51405039-175
Brand Honeywell
Origin USA
Operating Temp -40 to +70 deg C
Power Consumption ~6 W typical
Part Number 51405039-175
Channels 16 channels (12 single-ended, 4 differential)
Input Ranges 0-5 V, 1-5 V, 0.4-2 V, 4-20 mA (via internal 250 ohm resistor)
Resolution 16 bits
Scan Rate 50 ms

Channel-to-Channel Isolation and 4-20 mA HART Loop Protocol Execution

The Honeywell CC-PAIH02 51405039-175 analog input module digitizes process variables using a 16-bit A/D converter across a 50 ms scan rate cycle. Each channel interfaces directly with 2-wire or self-powered field transmitters utilizing the 4-20 mA HART loop protocol, as well as 0-5 V, 1-5 V, and 0.4-2 V voltage signals. The internal circuit architecture provides channel-to-channel isolation and common-mode noise suppression to safeguard backplane communications against field-side electrical interference and ground loop offsets.

Frequently Asked Questions

Q: How does the CC-PAIH02 51405039-175 module handle 4-20 mA current signals?

A: Current loop signals are converted internally across precision 250 ohm dropping resistors built into the module input circuit.

Q: Can single-ended and differential inputs be used simultaneously on the same CC-PAIH02 51405039-175 module?

A: Yes, the hardware layout supports up to 12 single-ended channels and 4 differential channels concurrently as designated on the corresponding IOTA terminal block.

Field Installation Guidelines

  1. Mount the Series-C IOTA base firmly onto the cabinet DIN rail or frame before seating the module.
  2. Align the module rear edge connector with the IOTA receptacle and press firmly until the mechanical locking tabs engage.
  3. Terminate field 4-20 mA or voltage signal conductors onto the assigned IOTA terminal terminals, checking for correct polarity.
  4. Route low-voltage analog input signal cabling in segregated wire troughs at least 200 mm away from high-voltage AC conductors.
  5. Ground signal cable shield drain wires at a single point on the cabinet earthing bus bar to prevent ground current loops.

How to Get a Quote

Order Tracking

Shipping Carriers

Refund Policy and Conditions

Warranty Conditions

Related Products