Honeywell CC-PDOB01 Digital Output 24V Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: CC-PDOB01

  • Condition: 10 Items in Stock

  • Product Type: Digital Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 3000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Honeywell CC-PDOB01 is a 32-channel 24V bussed digital output card designed for Experion C300 I/O systems. It provides discrete switching control for field devices by driving 24 VDC loads up to a maximum continuous voltage limit of 30 VDC.

Electrical Performance and Output Characteristics

Each of the 32 output channels delivers a typical on-state voltage of 24 V at a 0.5 A load current, maintaining low off-state leakage current below 0.5 uA. Under no-load conditions, the off-state indicated voltage reaches a maximum of 3.3 VDC, dropping to 0V VDC max under load. The module features dynamic switching response times with turn-on and turn-off delays not exceeding 10 ms.

Isolation and System Protection

To safeguard controller electronics against electrical transients and ground loops, the module incorporates robust galvanic isolation rated at 1500 VAC RMS or ±1500 VDC. This isolation barrier separates internal backplane logic from external field-side wiring loops.

Parameter Specification
Model CC-PDOB01
Brand Honeywell
Product Type Digital Output 24V Module
Number of Channels 32
Output Architecture Bussed Out
Maximum Load Voltage 30 VDC
On-State Voltage 24 V (typ) @ 0.5 A load current
Off-State Voltage 0 VDC max (3.3 VDC max indicated under no-load)
Off-State Leakage Current 0.5 uA max
Turn-On / Turn-Off Time 10 ms max
Galvanic Isolation 1500 VAC RMS or +/-1500 VDC
Shipping Weight 3 kg

Frequently Asked Questions

Q: What is the isolation capability of the Honeywell CC-PDOB01 digital output module?

A: The module provides high-level galvanic isolation rated at 1500 VAC RMS or +/-1500 VDC between system logic and field circuits.

Q: What are the switching response times and off-state leakage characteristics for each output channel?

A: Turn-on and turn-off response times are 10 ms maximum per channel, with off-state leakage current maintained below 0.5 uA.

How to Get a Quote

Order Tracking

Shipping Carriers

Refund Policy and Conditions

Warranty Conditions