Honeywell CC-TAIM01 51305959-175 Analog Input Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: CC-TAIM01 51305959-175

  • Condition: 10 Items in Stock

  • Product Type: Analog Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 5000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Honeywell CC-TAIM01 51305959-175, also cataloged as the CC-TAIM01 Analog Input Module, operates as a dedicated hardware component for millivolt signal acquisition and RTD resistance processing within Experion PKS Series C platforms.

Hardware Specifications

Parameter Specification
Model CC-TAIM01 51305959-175
Brand Honeywell
Origin USA
Operating Temp -40 to +70 deg C
Power Consumption 24 VDC IOTA bus supply
Module Type Low Level Analog Input Multiplexer Card
Part Number 51305959-175
Sensor Support Thermocouples (TC) and Resistance Temperature Detectors (RTD)
Environmental Protection G3 conformal coating
Diagnostics Configurable upscale or downscale sensor burnout detection

Cold Junction Compensation & Channel-to-Channel Isolation

The CC-TAIM01 module utilizes dedicated Cold Junction Compensation (CJC) algorithms and reference junction hardware to maintain measurement accuracy across temperature-critical thermocouple channels. Integrated differential multiplexing circuits combined with high-order analog filtering isolate incoming millivolt-level signals from high-frequency electromagnetic noise. Channel-to-channel isolation barriers prevent ground loop currents from skewing low-amplitude signal paths, delivering stable temperature readings into the Experion PKS Control Execution Environment (CEE).

Frequently Asked Questions

Q: How does the CC-TAIM01 handle a broken or disconnected thermocouple sensor?

A: Each channel features configurable upscale or downscale burnout detection that automatically flags open-circuit conditions to the controller, preventing stale data from affecting control logic.

Q: Can different thermocouple types be wired to channels on the same CC-TAIM01 module?

A: Yes, channels are individually software-configurable for distinct thermocouple types or RTD curves, provided appropriate compensation wiring is landed at the terminal assembly.

Q: What environmental protections are built into the -175 hardware revision?

A: The -175 revision includes standard G3 conformal coating, protecting internal circuitry against airborne corrosives, moisture, and chemical vapors.

Field Installation Guidelines

  1. Mount the CC-TAIM01 vertically onto its designated Series C IOTA slot until the mechanical retention clips fully lock.
  2. Terminate thermocouple extension wires or RTD leads using shielded, twisted-pair cabling directly to the IOTA screw terminal block.
  3. Connect the cable shield drain wire to the cabinet single-point ground bar to minimize common-mode voltage interference.
  4. Verify that Cold Junction Compensation sensors on the terminal assembly are installed and isolated from direct cabinet thermal discharge.

How to Get a Quote

Order Tracking

Shipping Carriers

Refund Policy and Conditions

Warranty Conditions

Related Products