Honeywell CC-TAIM01 51305959-175 Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: CC-TAIM01 51305959-175
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 5000g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell CC-TAIM01 51305959-175, also cataloged as the CC-TAIM01 Analog Input Module, operates as a dedicated hardware component for millivolt signal acquisition and RTD resistance processing within Experion PKS Series C platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-TAIM01 51305959-175 |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | 24 VDC IOTA bus supply |
| Module Type | Low Level Analog Input Multiplexer Card |
| Part Number | 51305959-175 |
| Sensor Support | Thermocouples (TC) and Resistance Temperature Detectors (RTD) |
| Environmental Protection | G3 conformal coating |
| Diagnostics | Configurable upscale or downscale sensor burnout detection |
Cold Junction Compensation & Channel-to-Channel Isolation
The CC-TAIM01 module utilizes dedicated Cold Junction Compensation (CJC) algorithms and reference junction hardware to maintain measurement accuracy across temperature-critical thermocouple channels. Integrated differential multiplexing circuits combined with high-order analog filtering isolate incoming millivolt-level signals from high-frequency electromagnetic noise. Channel-to-channel isolation barriers prevent ground loop currents from skewing low-amplitude signal paths, delivering stable temperature readings into the Experion PKS Control Execution Environment (CEE).
Frequently Asked Questions
Q: How does the CC-TAIM01 handle a broken or disconnected thermocouple sensor?
A: Each channel features configurable upscale or downscale burnout detection that automatically flags open-circuit conditions to the controller, preventing stale data from affecting control logic.
Q: Can different thermocouple types be wired to channels on the same CC-TAIM01 module?
A: Yes, channels are individually software-configurable for distinct thermocouple types or RTD curves, provided appropriate compensation wiring is landed at the terminal assembly.
Q: What environmental protections are built into the -175 hardware revision?
A: The -175 revision includes standard G3 conformal coating, protecting internal circuitry against airborne corrosives, moisture, and chemical vapors.
Field Installation Guidelines
- Mount the CC-TAIM01 vertically onto its designated Series C IOTA slot until the mechanical retention clips fully lock.
- Terminate thermocouple extension wires or RTD leads using shielded, twisted-pair cabling directly to the IOTA screw terminal block.
- Connect the cable shield drain wire to the cabinet single-point ground bar to minimize common-mode voltage interference.
- Verify that Cold Junction Compensation sensors on the terminal assembly are installed and isolated from direct cabinet thermal discharge.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions
Related Products