Honeywell FC-TSDI-16UNI Safety Manager System Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: FC-TSDL-16UNI

  • Condition: 10 Items in Stock

  • Product Type: Digital Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Honeywell FC-TSDI-16UNI, also cataloged as the FC-TSDI-16UNI Safety Manager System Module, operates as a dedicated hardware component for safe 16-channel discrete input processing within Honeywell Safety Manager platforms.

Hardware Specifications

Parameter Specification
Model FC-TSDI-16UNI
Brand Honeywell
Origin USA
Weight Shipping Weight: 2 kg
Dimensions 90 x 70 x 60 mm (L x W x H)
Operating Temp -20 to 70 deg C (standard panel ambient)
Power Consumption Power consumption dependent on backplane and loop excitation draw
Module Type Safety Manager System Module
Channels 16 channels (2 groups of 8)
Maximum Voltage Rating 50 VDC (IEC 61010-1 Overvoltage Category 3), 150 VDC (IEC 61010-1 Overvoltage Category 2)
Rail Mounting DIN EN rails TS32 / TS35 x 7.5 (Used length: 91 mm / 3.58 in)
Fuse Specification 250 mAT slow-acting (5 x 20 mm / 0.2 x 0.79 in)
Field Terminals Screw terminals, max wire size 2.5 mm2 (AWG 14), strip length 7 mm, tightening torque 0.5 Nm (0.37 ft-lb)
Certifications CE, TUV, UL, CSA, FM

4-20 mA HART Loop Protocol & Channel-to-Channel Isolation

Designed for critical discrete input monitoring in safety-instrumented setups, the module provides isolated field contact interfacing across two distinct groups of 8 channels. Internal channel-to-channel isolation de-couples field-side potential differences, preventing ground loops and stray high-voltage transients from degrading signal accuracy or interfering with adjacent analog 4-20 mA HART instrument wiring runs within the same control enclosure.

Frequently Asked Questions

Q: What are the electrical wiring limits for field connections on the FC-TSDI-16UNI screw terminal block?

A: The integral screw terminals accept a maximum wire cross-section of 2.5 mm2 (AWG 14) with a strip length of 7 mm (0.28 in) and must be torqued to 0.5 Nm (0.37 ft-lb).

Q: How is individual channel group protection handled on this module?

A: Circuit protection is enforced using an internal 250 mAT slow-acting fuse measuring 5 x 20 mm, designed to interrupt overcurrent conditions on field lines before affecting central backplane logic.

Field Installation Guidelines

  • Isolate all field power sources and rack backplane power before attaching or removing module wiring harnesses.
  • Mount the assembly securely onto standard TS32 or TS35 x 7.5 DIN rails, ensuring a minimum rail length engagement of 91 mm.
  • Strip field conductors to exactly 7 mm and tighten screw terminals to 0.5 Nm to prevent loose contacts or thermal stress.
  • Maintain separate raceways for discrete input field cables to avoid electromagnetic cross-talk from high-voltage AC cables.
  • Connect all field cable shield drain wires to a central ground bus at a single point to maintain isolation integrity.