Honeywell FC-TSGAS-1624 Safe Digital Input Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: FC-TSGAS-1624

  • Condition: 10 Items in Stock

  • Product Type: Digital Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 450g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Honeywell FC-TSGAS-1624, also cataloged as the FC-TSGAS-1624 Safe Digital Input Module, operates as a dedicated hardware component for safety-critical digital and field loop signal processing within Honeywell Safety Manager systems.

Hardware Specifications

Parameter Specification
Model FC-TSGAS-1624
Brand Honeywell
Dimensions 225 x 70 x 60 mm (8.86 x 2.76 x 2.36 in)
Operating Temp 0 to 70 deg C (module ambient derating limits)
Power Consumption 24 VDC external, 3 mA (excluding field loads)
Number of Input Channels 16 (common 0 V)
Input Current Range 0-25 mA
Input Resistance 500 Ohm (+/- 5%)
Output to SAI-1620m Module 0-4 VDC, Accuracy: 0.1%
Integrated Fuse Rating 500 mA (5 x 20 mm, 250 VAC / 300 VDC, Schurter PN 0001.2501)
Fuse Derating Linear from 0.5 A at 25 deg C to 0.35 A at 70 deg C
Signal Wire Termination Screw Terminals, Max 2.5 mm2 (AWG 14), Strip 7 mm, Torque 0.5 Nm
Power Wire Termination Screw Terminals (A, B), Max 16 mm2 (AWG 8), Strip 7 mm, Torque 1.2 Nm

Safety Loop Signal Condition & Channel-to-Channel Isolation

Engineered for safety instrumented architecture, the module processes field loop inputs across its 16 channels via a 500 Ohm input resistance network. The hardware interface conditions incoming 0-25 mA analog loops into a precise 0-4 VDC secondary output directed to the SAI-1620m module with an execution accuracy of 0.1%. Internal overcurrent protection relies on dedicated Schurter 500 mA ceramic fuses with strict linear derating profiles up to 70 deg C, preserving high safety integrity and predictable failure behaviors under abnormal field fault states.

Frequently Asked Questions

Q: What are the strict terminal torque limits required during wiring maintenance?

A: Signal screw terminals accepting wire up to 2.5 mm2 (AWG 14) require a maximum torque of 0.5 Nm (0.37 ft-lb). Main power screw terminals (A, B) accepting up to 16 mm2 (AWG 8) must be torqued precisely to 1.2 Nm (0.88 ft-lb) to ensure gas-tight electrical contact and eliminate thermal hotspots.

Q: How does ambient operating temperature impact module fusing?

A: The onboard 500 mA Schurter fuse operates under a defined linear derating curve. While providing full 0.5 A overcurrent rating at 25 deg C, its safe continuous capacity linearly degrades to 0.35 A at elevated module ambient temperatures reaching 70 deg C.

Field Installation Guidelines

  • Ensure primary power supplies are completely disconnected prior to inserting or removing field wiring terminations or replacing the internal 500 mA fuse.
  • Strip all signal and power conductor ends strictly to 7 mm (0.28 in) to prevent exposed metallic conductors outside the terminal block shell.
  • Connect 24 VDC power conductors using wire sizes up to 16 mm2 (AWG 8) and secure using a calibrated torque screwdriver set to 1.2 Nm.
  • Route low-voltage 0-25 mA / 0-4 VDC signal lines in dedicated, grounded conduits physically segregated from high-voltage AC power cabling to suppress electromagnetic interference.
  • Ground all field cable shields at a single point on the enclosure earth bus to eliminate ground loop currents across channel signal paths.