Honeywell MC-GAIH13 51304718-175 High Level Analog Input
Specifications
Manufacturer: Honeywell
Product No.: MC-GAIH13 51304718-175
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 2000g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell MC-GAIH13 51304718-175, also cataloged as the MC-GAIH13 High Level Analog Input / Smart Transmitter Interface (HLAI/STI) Field Termination Assembly (FTA), operates as a dedicated hardware component for galvanic isolation and signal processing of high-level analog inputs within Honeywell DCS platforms. Supporting up to 16 channels, the module conditions field transmitter signals under intrinsically safe (GI/IS) requirements, converting analog process variables into isolated system-level inputs via compression terminals.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MC-GAIH13 (51304718-175) |
| Brand | Honeywell |
| Origin | USA |
| Weight | 2.0 kg |
| Dimensions | Size B - 307 mm (12 inches) |
| Operating Temp | -40 to 70 deg C |
| Power Consumption | System Backplane Powered |
| Part Number | 51304718-175 |
| Module Type | High Level Analog Input / STI FTA |
| Channels | 16 Galvanically Isolated Channels |
| Isolation Type | Galvanic Isolation / Intrinsic Safety (GI/IS) |
| Terminal Type | Compression Terminals |
| Redundancy | Supported |
4-20 mA HART Loop Protocol & Channel-to-Channel Isolation
The Honeywell MC-GAIH13 51304718-175 incorporates individual channel-to-channel galvanic isolation barriers across all 16 analog inputs to eliminate ground potential differences between field sensors and controller backplanes. Fully compatible with 4-20 mA HART loop protocol field instruments, the assembly routes bi-directional digital frequency shift keying (FSK) communications without attenuating the primary analog current signal. This hardware-level isolation prevents cross-talk and protects system logic against high-voltage field transients.
Frequently Asked Questions
Q: Does the MC-GAIH13 51304718-175 support redundant processor configurations?
A: Yes, the module features dual cable interface ports designed to connect with redundant High-Performance Process Manager (HPM) or Experion I/O card racks without losing channel isolation.
Q: How does galvanic isolation function on the 16 input channels?
A: Integrated transformer and optical isolators physically separate the field wiring loop from the internal backplane logic, preventing high ground fault currents from damaging controller electronics.
Q: Can smart transmitters utilizing HART protocol communicate through this FTA?
A: Yes, the internal signal conditioning paths are structured to pass 4-20 mA DC current signals alongside high-frequency HART digital data streams without signal distortion.
Field Installation Guidelines
- Turn off backplane power and field loop supplies prior to installing or servicing the MC-GAIH13 board in the enclosure cabinet.
- Secure the 307 mm Size B board into the designated mounting channel, verifying that chassis earth grounding leads are firmly clamped.
- Attach multi-conductor interface cables between the FTA connector headers and the redundant I/O module rack.
- Strip field conductor wires to the recommended length and insert them into the compression terminals, tightening screws to standard industrial torque specifications.
- Ensure overall signal cable shields are grounded at a single chassis grounding bar to maintain proper noise immunity and galvanic isolation integrity.