Honeywell MC-PAOY22 Analog Output Module | 80363969-150

Specifications

  • Manufacturer: Honeywell

  • Product No.: MU-PAOY22 80363969-150

  • Condition: 10 Items in Stock

  • Product Type: Analog Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

Configured for current loop control execution and field final element actuation in Honeywell High-Performance Process Manager platforms, the Honeywell 80363969-150 (MC-PAOY22 Analog Output Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model MC-PAOY22
Brand Honeywell
Origin USA
Weight 1.50 kg
Operating Temp 0 to 60 deg C
Power Consumption Standard backplane power load
Part Number 80363969-150
Module Type Analog Output 16 Processor (16 Outputs), Conformal Coated
Output Channels 16 analog output channels
Signal Range 4-20 mA current loop

4-20 mA HART Loop Protocol & Channel-to-Channel Isolation

The MC-PAOY22 module provides 16 conformal-coated channels for precision current loop control. Operating in conjunction with 4-20 mA HART loop protocol field devices, internal digital-to-analog conversion circuits output continuous control signals to positioners and actuators. Channel-to-channel isolation limits ground loop currents and cross-talk, preserving signal integrity across parallel field circuits.

Frequently Asked Questions

Q: Does the conformal coating on the 80363969-150 module alter electrical installation requirements?

A: No. Conformal coating provides environmental protection against airborne contaminants but does not alter pinout, backplane connections, or field wiring procedures.

Q: Can the MC-PAOY22 module be replaced while the chassis backplane remains powered?

A: Module removal must follow standard Honeywell I/O maintenance procedures. Isolate external loop power and release module retaining hardware before extraction to prevent transient signal disruptions.

Q: How does channel-to-channel isolation impact current loop performance?

A: It isolates individual 4-20 mA output channels electrically, preventing potential differences between field grounding points from affecting neighboring loops.

Field Installation Guidelines

  • Verify backplane keying alignment prior to seating the MC-PAOY22 card into the rack slot.
  • Fully engage rear bus connectors and tighten top and bottom retaining screws to establish chassis ground continuity.
  • Route 4-20 mA analog output conductors in shielded twisted-pair cabling separated from high-voltage AC lines.
  • Ground all field cable shield drain wires at a single central system instrumentation earth grounding bar.
  • Wear an ESD wrist strap connected to chassis ground during module handling to protect sensitive analog electronics.