Honeywell MU-TAOY22 51204172-125 Analog Output Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: MU-TAOY22 51204172-125

  • Condition: 10 Items in Stock

  • Product Type: Analog Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Honeywell MU-TAOY22 51204172-125, also cataloged as the MU-TAOY22 Analog Output Module, operates as a dedicated hardware component for 16-channel current loop signal synthesis within Honeywell TDC 3000 systems.

Hardware Specifications

Parameter Specification
Model MU-TAOY22
Brand Honeywell
Origin USA
Weight 2 kg (shipping)
Operating Temp 0 to 60 deg C
Power Consumption 24 VDC bus-powered
Part Number 51204172-125
Module Type Analog Output 16-Point Processor / FTA
Output Signal Range 4-20 mA (settable 0 mA, 2.9 mA to 21.1 mA)
Resolution 0.05%
Calibrated Accuracy +/-0.35% Full Scale at 25 deg C
Maximum Load Resistance 750 ohms at 20 mA

4-20 mA HART Loop Protocol & Channel Isolation

Engineered for precise final control element drive, this module delivers 16 isolated current loops with integrated output readback diagnostics. Channel architecture maintains a dynamic compliance voltage up to 15 V at 20 mA across a 750 ohm resistive load. The internal circuitry limits total output ripple to less than 100 mV peak-to-peak at power line frequencies, suppressing high-frequency crosstalk and maintaining signal linearity within +/-0.05% across the entire analog control loop execution path.

Frequently Asked Questions

Q: What is the maximum load resistance supported by the MU-TAOY22 output channels at full 20 mA drive?

A: The module supports a maximum resistive load of 750 ohms at 20 mA when supplied with a nominal 24 V source voltage.

Q: How does the output stage handle open-circuit field wiring conditions?

A: Integrated output readback diagnostics compare requested current commands against actual loop feedback (+/-4% readback accuracy limit), triggering hardware status flags upon detecting an open loop or degraded field loop circuit.

Q: Can the output current range exceed standard 4-20 mA operational limits during loop testing?

A: Yes, the channel current limits can be directly set from 0 mA or between 2.9 mA and 21.1 mA, with an absolute hard upper current limit clamp at 24 mA.

Field Installation Guidelines

  • Fully de-energize the host I/O rack supply before seating the module assembly into the cabinet backplane.
  • Connect field loop conductors securely to the compression terminal block, verifying pin assignments to prevent reverse polarity on active positioners.
  • Route analog output wiring away from three-phase AC power lines and high-current motor leads to prevent electromagnetic interference coupling.
  • Ground all field cable overall shields at the single point earth bus bar inside the termination cabinet.
  • Observe static discharge procedures, including wearing a grounded ESD wrist strap, whenever touching exposed edge connectors.