Honeywell MU-TAOY22 51204172-125 Analog Output Module
Specifications
Manufacturer: Honeywell
Product No.: MU-TAOY22 51204172-125
Condition: 10 Items in Stock
Product Type: Analog Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 2000g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell MU-TAOY22 51204172-125, also cataloged as the MU-TAOY22 Analog Output Module, operates as a dedicated hardware component for 16-channel current loop signal synthesis within Honeywell TDC 3000 systems.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MU-TAOY22 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 2 kg (shipping) |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 24 VDC bus-powered |
| Part Number | 51204172-125 |
| Module Type | Analog Output 16-Point Processor / FTA |
| Output Signal Range | 4-20 mA (settable 0 mA, 2.9 mA to 21.1 mA) |
| Resolution | 0.05% |
| Calibrated Accuracy | +/-0.35% Full Scale at 25 deg C |
| Maximum Load Resistance | 750 ohms at 20 mA |
4-20 mA HART Loop Protocol & Channel Isolation
Engineered for precise final control element drive, this module delivers 16 isolated current loops with integrated output readback diagnostics. Channel architecture maintains a dynamic compliance voltage up to 15 V at 20 mA across a 750 ohm resistive load. The internal circuitry limits total output ripple to less than 100 mV peak-to-peak at power line frequencies, suppressing high-frequency crosstalk and maintaining signal linearity within +/-0.05% across the entire analog control loop execution path.
Frequently Asked Questions
Q: What is the maximum load resistance supported by the MU-TAOY22 output channels at full 20 mA drive?
A: The module supports a maximum resistive load of 750 ohms at 20 mA when supplied with a nominal 24 V source voltage.
Q: How does the output stage handle open-circuit field wiring conditions?
A: Integrated output readback diagnostics compare requested current commands against actual loop feedback (+/-4% readback accuracy limit), triggering hardware status flags upon detecting an open loop or degraded field loop circuit.
Q: Can the output current range exceed standard 4-20 mA operational limits during loop testing?
A: Yes, the channel current limits can be directly set from 0 mA or between 2.9 mA and 21.1 mA, with an absolute hard upper current limit clamp at 24 mA.
Field Installation Guidelines
- Fully de-energize the host I/O rack supply before seating the module assembly into the cabinet backplane.
- Connect field loop conductors securely to the compression terminal block, verifying pin assignments to prevent reverse polarity on active positioners.
- Route analog output wiring away from three-phase AC power lines and high-current motor leads to prevent electromagnetic interference coupling.
- Ground all field cable overall shields at the single point earth bus bar inside the termination cabinet.
- Observe static discharge procedures, including wearing a grounded ESD wrist strap, whenever touching exposed edge connectors.