Honeywell MU-TDID12 51304441-100 Digital Input FTA Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: MU-TDID12 53104441-100

  • Condition: 10 Items in Stock

  • Product Type: Digital Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 200g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

Configured for discrete field status monitoring and voltage-level detection in PM/APM/HPM controller architectures, the Honeywell MU-TDID12 (51304441-100 Digital Input Module) provides direct physical/electrical execution across 32 field channels. It conditions 24 VDC binary signals from field switches and contacts, optical isolation barriers, and noise-filtering circuits to transfer discrete IO states to the DCS backplane within a maximum processing delay of 2.0 ms.

Hardware Specifications

Parameter Specification
Model MU-TDID12 (51304441-100)
Brand Honeywell
Origin USA
Operating Temp 0 to 60 deg C
Power Consumption 20-30 VDC Field Input Range
Channel Count 32 Digital Input Channels
Isolation Voltage 1500 VAC rms or +/-1500 VDC
Sense Current ON: 4.5 mA min / OFF: 2.8 mA max
Voltage Thresholds Pick-Up (ON): 20 VDC min / Drop-Out (OFF): 10 VDC max
Input Frequency DC to 15 Hz
Response Time 2.0 ms max filter and isolation delay
Surge Compliance ANSI/IEEE C37.90.1-1978

Channel-to-Channel Isolation & Signal Protection

The MU-TDID12 (51304441-100) utilizes removable plug-in optical isolators to establish a 1500 VAC rms / +/-1500 VDC isolation barrier between field-side wiring and internal process manager buses. This architecture isolates sensitive controller electronics from field-induced transients, common-mode noise, and ground loops. Channel-to-channel isolation safeguards individual processing paths, preventing cross-talk and high-voltage surge propagation from impairing adjacent discrete inputs or disturbing parallel 4-20 mA HART loop protocol wiring within shared marshalling panels.

Frequently Asked Questions

Q: Are individual optical isolators on the MU-TDID12 field-replaceable while maintaining system integrity?

A: Yes, the assembly integrates socketed, removable plug-in isolators that permit single-channel maintenance without disassembling the primary circuit board or disconnecting field wiring terminals.

Q: How does the module handle voltage transients generated by field contact switching?

A: Each input channel complies with ANSI/IEEE C37.90.1-1978 surge withstand capability standards, suppressing voltage spikes before signal propagation through the 2.0 ms input filter circuit.

Field Installation Guidelines

  1. Mount the Field Termination Assembly (FTA) securely on standard cabinet DIN rail structures or mounting channels.
  2. Verify field supply voltage remains within the 20-30 VDC operating window prior to energizing input loops.
  3. Terminate incoming field wiring at designated screw terminals, ensuring cable shields tie to the system ground bus at a single cabinet point.
  4. Maintain physical separation between 24 VDC digital input signal cables and high-voltage AC power lines to prevent electromagnetic interference.

How to Get a Quote

Order Tracking

Shipping Carriers

Refund Policy and Conditions