Honeywell TC-ODD321 Experion DC Output Module
Specifications
Manufacturer: Honeywell
Product No.: TC-ODD321
Condition: 10 Items in Stock
Product Type: Digital Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 1500g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell TC-ODD321 is a high-density 32-channel discrete DC output module designed for Honeywell Experion control systems. It provides switching logic and actuation power for field devices such as solenoids, relays, and indicator lights across two isolated 16-point groups.
Voltage Thermal Derating and Surge Capacity
The module operates across a flexible DC voltage output range that features linear derating based on ambient operating temperature, providing 10 to 31.2 VDC at up to 50 deg C and 10 to 28 VDC at 60 deg C. Each channel supports a surge current of 1 A for 10 ms (repeatable every 2 s at 60 deg C) to handle inrush currents from inductive loads.
Output Load Limits and Interfacing
To ensure valid state switching, each point requires a minimum on-state load current of 3.0 mA. Maximum on-state voltage drop is rated at 1 VDC at rated current per point (3 VDC under IEC 1131-2 conditions). Total power dissipation for the module is 6.1 W, and field wiring interfaces via the TC-TBCH 36-position terminal block.
| Parameter | Specification |
|---|---|
| Model | TC-ODD321 |
| Brand | Honeywell |
| System Compatibility | Experion |
| Product Type | DC Output Module |
| Number of Outputs | 32 (16 points per common) |
| Output Voltage Range | 10 to 31.2 VDC at 50 deg C (linear derating), 10 to 28 VDC at 60 deg C |
| Surge Current | 1 A for 10 ms (repeatable every 2 s at 60 deg C) |
| Minimum On-State Current Load | 3.0 mA per output |
| Maximum On-State Voltage Drop | 1 VDC at rated current per point (3 VDC per IEC 1131-2) |
| Power Dissipation | 6.1 W |
| Connection Terminal Block | TC-TBCH (36-position terminal block) |
| Shipping Weight | 1.5 kg |
Frequently Asked Questions
Q: How are the output channels grouped on the TC-ODD321 module?
A: The 32 output channels are split into two commons with 16 points per common.
Q: What is the maximum surge current capacity for individual outputs on the TC-ODD321?
A: Each output channel can handle a surge current of 1 A for 10 ms, repeatable every 2 seconds at 60 deg C.
Q: Which terminal block is required to interface field wiring to the TC-ODD321?
A: Field wiring connects using the TC-TBCH 36-position terminal block.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions
Related Products