Honeywell TC-RPSCA2 Redundant Power System Chassis Adapter
Specifications
Manufacturer: Honeywell
Product No.: TC-RPSCA2
Condition: 10 Items in Stock
Product Type: Redundant Power Supply Chassis Adapters
Product Origin: USA
Payment:T/T, Western Union
Weight: 400g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell TC-RPSCA2, also cataloged as the TC-RPSCA2 Redundant Power Supply Chassis Adapter, operates as a dedicated hardware component for multi-rail DC power distribution and redundant switchover management within Honeywell Experion PKS and TDC 3000 systems.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-RPSCA2 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.4 kg |
| Dimensions | Standard Form Factor |
| Operating Temp | -25 to +70 deg C |
| Power Consumption | Multi-rail output: 5.1 VDC (15 A), 24 VDC (2.8 A), 3.3 VDC (4 A), 1.2 VDC (1.5 A) |
| Product Type | Redundant Power Supply Chassis Adapter |
| System Compatibility | Honeywell Experion PKS, TDC 3000 |
| Circuit Protection | Integrated overload, short-circuit, and thermal protection |
| Humidity Limits | 5% to 95% Non-condensing |
4-20 mA HART Loop and Channel Isolation Features
The TC-RPSCA2 adapter manages multi-bus output power routing directly across Experion PKS backplane topologies. The unit incorporates channel-to-channel power isolation mechanisms to prevent local power rail disturbances from bleeding into process signal backplanes. By delivering regulated, low-ripple 24 VDC and 5.1 VDC rails, the adapter ensures stable supply voltages for field I/O modules, preventing power line noise from corrupting 4-20 mA HART loop communication networks and precision analog inputs.
Frequently Asked Questions
Q: What multi-rail DC voltage outputs are delivered through the TC-RPSCA2 chassis backplane?
A: The adapter routes four regulated DC power buses to the system backplane: 5.1 VDC at up to 15 A, 24 VDC at 2.8 A, 3.3 VDC at 4 A, and 1.2 VDC at 1.5 A.
Q: How does the unit maintain power continuity during a power module failure?
A: The adapter incorporates dual-input power blending and diode ORing circuitry that automatically shifts load execution between redundant power modules without output voltage dropouts or controller reboots.
Q: What happens if the 5.1 VDC power rail load exceeds 15 A?
A: Exceeding the 15 A threshold on the primary 5.1 VDC rail triggers internal overcurrent or thermal protection stages, which may force an emergency shutdown to protect system logic components.
Field Installation Guidelines
- Ensure all primary input power sources to the power chassis are completely de-energized prior to installing or removing the adapter module.
- Securely tighten all mechanical chassis retention screws to guarantee low-impedance electrical contact along high-current 5.1 VDC and 24 VDC bus bars.
- Maintain at least 50 mm of unobstructed vertical ventilation space above and below the rack frame to prevent thermal trapping around DC conversion stages.
- Connect power feeds to two separate, galvanically isolated supply sources to establish true fault-tolerant electrical redundancy.
- Route all system ground connections directly to the master cabinet grounding bus bar using short, heavy-gauge copper wiring to suppress common-mode electrical noise.