TC-IAH161 Experion PKS Process I/O Series High Level Analog Input Module | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: TC-IAH16I
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 1500g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
Configured for high-density analog signal acquisition in Experion PKS Process I/O platforms, the Honeywell TC-IAH161 (TC-IAH161 High Level Analog Input Module) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-IAH161 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 1.5 kg (Shipping Weight) |
| Dimensions | Standard Experion PKS chassis-mount module form factor |
| Operating Temp | 0 to +60 deg C standard chassis enclosure rating |
| Power Consumption | 4.1 W maximum power dissipation |
| Number of Points | 16 channels |
| Voltage Input Ranges | -10.25 to +10.25 VDC, 0 to 10.25 VDC, 0 to 5.125 VDC |
| Current Input Range | 0 to 20.5 mA (via internal 250 ohm resistor) |
| Resolution | 16 bits across each input range |
| Module Publish Rate | 250 msec |
| Input Impedance | Greater than 1.0 megohm (Voltage), 249 ohms nominal (Current) |
| Channel Bandwidth | 20 Hz (-3dB) |
| RFI Immunity | Error less than 2.0% of range at 10 V/m (27 to 1000 MHz) |
| User to System Isolation | 100% tested at 2550 VDC for 1s |
| Terminal Connection | TC-TBCH 36-position terminal block |
4-20 mA HART Loop Protocol & Channel-to-Channel Isolation
The TC-IAH161 processes up to 16 high-level current or voltage signals, converting field sensor levels into digital representations via 16-bit analog-to-digital convertors. Integrated 249 ohm precision resistors accommodate 0 to 20.5 mA current loops, allowing direct coupling with standard 4-20 mA HART loop protocol field transmitters. Physical isolation rated at 2550 VDC between user-side field wiring and internal backplane logic prevents field-induced surge transients and common-mode potential shifts from degrading system bus communication.
Frequently Asked Questions
Q: Does the TC-IAH161 module require external precision resistors for current loop operation?
A: No, the module integrates internal 250 ohm (249 ohm nominal) precision sensing resistors directly on the card to convert current signals to voltage.
Q: Can the TC-IAH161 module be hot-swapped while the rack backplane is energized?
A: Yes, the chassis interface design allows Online Insertion and Removal (RIUP/hot-swap) without disrupting adjacent I/O modules on the same backplane.
Q: What terminal block is required to interface field conductors to the TC-IAH161 card?
A: Field connections require the dedicated TC-TBCH 36-position removable terminal block.
Field Installation Guidelines
- Slide the TC-IAH161 module into its designated chassis slot along the card guide rails until the backplane connectors lock into place.
- Secure the module mechanically by tightening the top and bottom retaining screws onto the chassis frame.
- Wire field input conductors to the TC-TBCH 36-position terminal block, ensuring correct polarity for voltage or current loop configurations.
- Ground individual cable shield drain wires to the system cabinet earth bus bar to preserve signal integrity against external high-frequency RF interference.