TC-IDK161 | Honeywell | AC Digital Input Module
Specifications
Manufacturer: Honeywell
Product No.: TC-IDK161
Condition: 10 Items in Stock
Product Type: Digital Input Cards
Product Origin: USA
Payment:T/T, Western Union
Weight: 250g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Honeywell TC-IDK161, also cataloged as the TC-IDK161 AC Digital Input Module, operates as a dedicated hardware component for 120 VAC discrete signal detection and field-to-logic isolation within Honeywell DCS platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-IDK161 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.25 kg |
| Dimensions | 44.5 x 120 x 100 mm |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | Power Dissipation: 4.9 W |
| Input Voltage Range | 79 to 132 VAC |
| Line Frequency | 50/60 Hz |
| Input Current | 5 mA @ 79 V, 15 mA @ 132 V |
| Off-State Voltage (Max) | 20 VAC |
| Off-State Current (Max) | 2.5 mA |
| Input Impedance | 11 kohm @ 60 Hz |
| Isolation Voltage | 2546 VDC |
| Humidity Limits | 5% to 95% RH (non-condensing) |
Channel-to-Channel Isolation and Loop Integrity
The TC-IDK161 features robust optical and electrical isolation barriers rated up to 2546 VDC between field input channels and backplane processing logic. This channel-to-channel isolation prevents high-voltage AC common-mode spikes, ground loops, and field wiring surges from damaging internal controller backplanes. By isolating AC field contacts from system logic, the module eliminates electromagnetic cross-talk that could otherwise couple into sensitive analog measurement sub-racks running 4-20 mA HART loop communication protocols.
Frequently Asked Questions
Q: What are the off-state threshold limits for the TC-IDK161 input channels?
A: An input channel registers an off-state logic condition when the incoming voltage drops below 20 VAC or when the leakage current does not exceed 2.5 mA.
Q: How is galvanic isolation structured across the TC-IDK161 module circuit?
A: The module incorporates a galvanic isolation barrier rated at 2546 VDC, separating 120 VAC field-side terminal circuitry from low-voltage backplane communication logic.
Q: Can the TC-IDK161 process DC discrete inputs?
A: No. The channel input network is engineered specifically for 50/60 Hz AC signals across the 79 to 132 VAC operational range with an nominal input impedance of 11 kohm at 60 Hz.
Field Installation Guidelines
- Isolate all external 120 VAC power sources feeding field dry contacts prior to connecting or disconnecting wiring harnesses from the module terminal block.
- Maintain clear physical separation inside cabinet raceways between high-voltage 120 VAC digital input lines and low-level analog or communication cables.
- Align the module card edge carefully with the rack guide rails and push firmly to ensure positive backplane connector mating and earth ground continuity.
- Connect field cable shields directly to the dedicated single-point ground bar inside the enclosure to mitigate high-frequency electrical noise.
- Verify cabinet convection airflow is unobstructed to keep module power dissipation (4.9 W max) from elevating enclosure ambient temperature above +70 deg C.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions
Related Products
- Choosing a selection results in a full page refresh.