TK-IXR061 Analog Input Module | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: TK-IXR061
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 800g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The TK-IXR061 is a dedicated analog input module manufactured by Honeywell for multi-channel signal acquisition and processing within Experion control system platforms. Engineered for high-precision industrial measurement, this module provides six isolated analog input channels supporting 0-10 VDC voltage and 4-20 mA current instrumentation circuits.
Signal Isolation and Measurement Precision
The module incorporates 500 Vrms galvanic isolation between individual channels and system ground to suppress ground loop currents and transient voltage coupling. Utilizing a 16-bit analog-to-digital converter providing 65,536 steps with an accuracy of +-0.05% of full scale, it ensures stable signal digitization across wide ambient thermal profiles with a temperature coefficient of +-3 ppm/deg C.
Field Installation Guidelines
Mount the module vertically on a standard 35 mm DIN rail inside protective industrial enclosures to maintain proper convection airflow. Maintain dedicated separation between 24 VDC field instrument wiring and high-voltage AC distribution conduits, and ensure all shield drain wires from field transmitter cables are bonded to a single cabinet ground point. Verify that input terminal blocks are locked securely and execute loop current testing prior to full controller commissioning.
| Parameter | Specification |
|---|---|
| Model | TK-IXR061 |
| Brand | Honeywell |
| Product Type | Analog Input Module |
| System Platform | Honeywell Experion control system |
| Input Channels | 6 isolated analog inputs |
| Input Signals | 0-10 VDC voltage, 4-20 mA current |
| Resolution & Accuracy | 16-bit (65,536 steps), +-0.05% of full scale |
| Temperature Coefficient | +-3 ppm/deg C |
| Load Impedance | Voltage > 2 kohm, Current < 600 ohm |
| Isolation Voltage | 500 Vrms channel-to-channel and channel-to-ground |
| Response Time | < 5 ms |
| Operating Voltage | 24 VDC (18 to 30 VDC range) |
| Power Consumption | Max 3.5 W (4.3 W max power dissipation) |
| Mounting Type | DIN rail (35 mm) |
| Operating Temp | -40 deg C to +70 deg C |
| Dimensions | 44.5 x 120 x 100 mm |
| Weight | 1.76 lbs |
Frequently Asked Questions
Q: Does the TK-IXR061 module support hot-swappable installation during system operation? A: Yes. The module features built-in circuit isolation that allows hot-swappable replacement under live cabinet power without disrupting adjacent I/O modules on the chassis rail.
Q: How does fault detection operate on active 4-20 mA input loops? A: The module continuously monitors loop impedance and current signal thresholds, flagging out-of-range conditions (< 3.8 mA or > 20.5 mA) and open-circuit wire breaks to the controller diagnostics layer.
How to Get a Quote
Order Tracking
Shipping Carriers
Refund Policy and Conditions
Warranty Conditions
Related Products
- Choosing a selection results in a full page refresh.