Triconex 3401 Digital Output Module

Specifications

  • Manufacturer: Triconex

  • Product No.: 3401

  • Condition: 10 Items in Stock

  • Product Type: Digital Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Triconex 3401 is a 16-channel digital output module engineered for safety-critical industrial applications. It features robust common-ground output switching with integrated diagnostic coverage, operating across a nominal 24 VDC range to ensure reliable control and fault detection in demanding environments.

Output Performance and Voltage Characteristics

The module delivers reliable digital signal switching across its 16 channels, supporting a typical switching current of 3.0 A with a self-limiting maximum below 4.8 A. It operates on a nominal 24 VDC supply within an operational voltage range of 15 VDC to 30 VDC, and accommodates an absolute maximum output voltage of 33 VDC.

Advanced Diagnostics and Loop-Back Monitoring

Built-in diagnostic functions monitor for open circuits, short circuits, power faults, and output states via continuous loop-back scanning. The loop-back mechanism completes a full scan of all 16 points in under 1.0 ms, utilizing specific voltage thresholds to distinguish between off regions, transition regions, and on states.

Environmental Adaptability

Designed to withstand unconditioned industrial settings, the unit functions reliably across a broad ambient temperature range of -40 deg C to 70 deg C. It also accommodates relative humidity levels from 5% to 95% under non-condensing conditions, supporting stable long-term operation in critical control loops.

Parameter Specification
Model 3401
Brand Triconex
Product Type Digital Output Module
Output Channels 16, common ground
Nominal Output Voltage 24 VDC
Operational Voltage Range 15 VDC to 30 VDC
Absolute Max Output Voltage 33 VDC
Switching Current < 4.8 A (self-limiting); 3.0 A typical
On-State Voltage Drop < 1.0 V DC @ 1.5 A
Leakage Current (Off State) < 1 mA
Loop-Back Scan Time < 1.0 ms for all 16 points
Operating Temperature -40 deg C to 70 deg C
Relative Humidity 5% to 95%, non-condensing

Frequently Asked Questions

Q: What is the nominal operating voltage and current rating for the Triconex 3401 module?

A: The module operates at a nominal 24 VDC (within an operational range of 15 VDC to 30 VDC) and supports a typical switching current of 3.0 A per channel, with a self-limiting maximum below 4.8 A.

Q: How does the module handle diagnostic monitoring and loop-back scans?

A: It provides continuous diagnostic coverage for open circuits, short circuits, and power faults, executing a full loop-back scan across all 16 points in under 1.0 ms.