Triconex 3601T TMR Digital Output Module | 3000307-055
Specifications
Manufacturer: Triconex
Product No.: 3601T 3000307-055
Condition: 10 Items in Stock
Product Type: Digital Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 1500g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
The Triconex 3601T (Model 3000307-055) is a high-reliability TMR digital output module engineered for safety-critical industrial control systems. It utilizes quadruplicated voting circuitry for fault-tolerant signal processing, ensuring uninterrupted operation and secure output control even during internal component faults.
Electrical Performance and Power Ratings
The module operates at a nominal 120 VDC across an allowable voltage range of 90 VDC to 150 VDC. It delivers a maximum current of 0.8 A per point while accommodating surge currents up to 4 A for 10 ms, with an on-state voltage drop of less than 1.5 V typical.
Isolation, Protection, and Diagnostics
Point-to-point electrical isolation spans 1500 VDC to 2500 VDC, and load leakage is restricted to a maximum of 2 mA alongside 4 mA chassis leakage at 60 Hz. Protection is provided by a 1.0 A fast-acting fuse per output, complemented by comprehensive diagnostic indicators including ON/OFF status per point, module-level PASS, FAULT, ACTIVE states, and individual load/fuse field alarms.
Physical Dimensions and Enclosure Specs
Built for standard industrial rack environments, the unit measures 20.3 cm × 12.7 cm × 5.1 cm and weighs 1.5 kg, facilitating seamless physical integration into Triconex safety system chassis.
| Parameter | Specification |
|---|---|
| Model | 3601T (3000307-055) |
| Brand | Triconex |
| Product Type | TMR Digital Output Module |
| Nominal Voltage | 120 VDC |
| Voltage Range | 90 to 150 VDC |
| Voltage Drop | < 1.5 V typical |
| Maximum Current | 0.8 A per point |
| Surge Current | 4 A for 10 ms |
| Load Leakage | 2 mA maximum |
| Chassis Leakage | 4 mA maximum @ 60 Hz |
| Point Isolation | 1500 VDC / 2500 VDC |
| Fuses | 1.0 A fast-acting fuse per output |
| Dimensions | 20.3 cm x 12.7 cm × 5.1 cm |
| Weight | 1.5 kg |
Frequently Asked Questions
Q: What is the nominal operating voltage and current limit for the Triconex 3601T module?
A: The module operates at a nominal 120 VDC (with an operational range of 90 to 150 VDC) and supports a maximum current of 0.8 A per point.
Q: How does the module handle electrical protection and fault monitoring?
A: Each output point features a 1.0 A fast-acting fuse and dedicated load/fuse field alarms, supported by module-level PASS, FAULT, and ACTIVE status indicators.